What This Requirement Covers
Condensation occurs when moist air comes into contact with a cold surface, causing the moisture to condense into water. In buildings, condensation can cause mould growth, timber decay, damage to finishes, and health problems for occupants. Preventing condensation requires a combination of adequate ventilation (Part F), insulation (Part L), and moisture resistance (Part C).
Key Requirements
Surface Condensation
- Occurs on cold surfaces such as windows, external walls, and thermal bridges
- Prevented by maintaining surface temperatures above the dew point of the indoor air
- Insulation raises internal surface temperatures (Part L)
- Ventilation removes moist air and replaces it with drier outside air (Part F)
- Heating raises air temperatures and reduces relative humidity
Interstitial Condensation
- Occurs within the building fabric when moisture vapour passes through the construction and condenses on a cold layer
- Prevented by:
- Condensation risk analysis should be carried out to BS EN ISO 13788 or BS 5250 for all new constructions
Cold Roofs and Warm Roofs
- Cold roofs (insulation at ceiling level): The roof void must be ventilated to remove moisture. Minimum ventilation: equivalent to a continuous 10 mm gap at the eaves on opposite sides, plus a 5 mm gap at the ridge for roofs with a pitch of 15 degrees or more
- Warm roofs (insulation at rafter level or above the deck): No ventilation of the roof void is required if a VCL is placed on the warm side of the insulation. A breather membrane must be used on the cold side
- Hybrid roofs (insulation both at ceiling and rafter level): Must be carefully designed to avoid trapping moisture between insulation layers
Subfloor Ventilation
- Suspended timber ground floors must have cross-ventilation beneath the floor to prevent moisture buildup
- Minimum ventilation: 1500 mm² per metre run of external wall, or equivalent to a 150 mm x 150 mm airbrick every 1.5 metres
- Airbricks must not be blocked or covered during landscaping or paving works
Practical Compliance Tips
- The three-pronged approach to condensation prevention is: insulate, ventilate, heat - all three must work together
- Ensure VCLs are continuous and sealed at joints; a gap in the VCL allows moisture to bypass it and condense within the construction
- In bathrooms and kitchens, always extract moist air directly to outside, never into a roof void or adjacent room
- Do not over-seal a building without providing adequate controlled ventilation; very airtight buildings need MVHR or continuous mechanical extract
- Specify insulated lintels and cavity closers to eliminate cold bridges around windows where condensation commonly forms
- In loft spaces, ensure insulation does not block eaves ventilation; use proprietary eaves ventilation trays
- Advise occupants to use extract fans, open windows, and avoid drying clothes indoors on radiators